Complies with the requirements of the UK Water Supply Regulations 1999 G18.3 and with Part G of the Building Regulation clause 3.63 tempering valves must be set to operate at a mixed water outlet temperature between 55 and 60 degrees celsius.
SPECIFICATION
Maximum inlet pressure : 10 bar static, 5 bar dynamic
Maximum inlet temperature : 90C
Certified to BS EN 15092
Maximum pressure ratio (H/C or C/H) : 2:1
Minimum temperature difference between hot water inlet and mixed water outlet for best performance : 10C
Temperatures setting range : 45-65C
BS EN set temperature range : 45-65C
Set water temperature : 55-65C
Temperature stability : 2C
Minimum flow rate for stable operation : 4 l/m - and sizes, 6 l/m -1 size
Please note that these product properties are not a replacement for the manufacturer's literature and it is always recommended that Altecnic is consulted before specifying.
|
|
||
| Flow Rate (?) | 4 l/min | |
| Max Pressure (bar) (?) | 5 bar | 53.33% |
| Static Pressure (?) | 10 bar | 48.28% |
|
|
||
| Uniclass (?) | Pr_65_54 Valve products | |
|
|
||
| Product ID Number (?) | 521814 | |
|
|
||
| Finish(es) (?) | DZR Chrome Plated | |
|
|
||
| Connection Type (?) | Male BSP | |