Series 5218 Thermostatic Mixing Valve

by Altecnic

Complies with the requirements of the UK Water Supply Regulations 1999 G18.3 and with Part G of the Building Regulation clause 3.63 tempering valves must be set to operate at a mixed water outlet temperature between 55 and 60 degrees celsius.


SPECIFICATION

Maximum inlet pressure : 10 bar static, 5 bar dynamic

Maximum inlet temperature : 90C

Certified to BS EN 15092

Maximum pressure ratio (H/C or C/H) : 2:1

Minimum temperature difference between hot water inlet and mixed water outlet for best performance : 10C

Temperatures setting range : 45-65C

BS EN set temperature range : 45-65C

Set water temperature : 55-65C

Temperature stability : 2C

Minimum flow rate for stable operation : 4 l/m - and sizes, 6 l/m -1 size