116 Series Thermostatic Regulator For Hot Water Re-circulation

by Altecnic

SPECIFICATION

The Altecnic thermostatic regulator for domestic hot water re-circulation systems automatically maintains the specified water temperature.

The regulator controls the flow rate in accordance with the inlet water temperature by means of a dedicated internal thermostatic cartridge. 

When the water temperature approaches the set value, the obturator progressively close and reduces the flow passage reducing the amount of water re-circulating. 

The water supplied by the re-circulation pump is available to be distributed to other branches in the system, resulting in effective automatic thermal balancing. 

Temperature gauge available. 

Insulation shell available upon request

Medium: Potable water

Kv maximum: 1.8 m3/h

Kv disinfection: 1.0 m3/h

Kv min at 58C (DN 15): 0.10 20% m3/h

Kv min at 58C (DN 20): 0.12 20% m3/h

Kv (Dt = 5K): 0.45 m3/h

Max. working pressure: 16 bar

Max. differential pressure: 1 bar

Temperature adjustment range: 35 to 60C

Factory setting: 52C

Disinfection temperature: 70C

Closing temperature: 75C

Connections - or female: BS EN 10226-1

Specification Details for 116 Series Thermostatic Regulator For Hot Water Re-circulation (Mixing Valves)

Please note that these product properties are not a replacement for the manufacturer's literature and it is always recommended that Altecnic is consulted before specifying.