Mixcal Careflo Plus TMV

by Altecnic

Thermostatic diverting valve with thermal disinfection The unique manual override function allows thermal disinfection against Legionella to be performed using the special tool. The special tool lifts the spindle, by-passing the operation of the thermostatic cartridge. The higher temperature hot water passes through the valve and pipework to thermally disinfect it.

Using the special tool and the manual override function allows thermal disinfection to be performed through to the outlets, so a complete flush can be performed not just a partial flush. Thermal disinfection helps protect the system against Legionella and other microbial organisms.

Specification

Max. working pressure: 10 bar - Static

Min. working pressure: 0.2 Bar : Dynamic

Max. inlet temperature: 85C

Inlet temperature range:

- hot supply: 55 - 65C

- cold supply: 0.5 - 20C

D 08 working pressure:

- low pressure: 0.2 - 1.0 Bar

- high pressure: 1.0 - 5.0 Bar

Max. inlet pressure ratio (H/C or C/H): 5:1

Accuracy: 2C

Setting Range: 30 to 50C

Min. temperature difference between inlet hot water and outlet mixed water: 10C

Min. flow for stable operation 4 l/m

Specification Details for Mixcal Careflo Plus TMV (Mixing Valves)

Please note that these product properties are not a replacement for the manufacturer's literature and it is always recommended that Altecnic is consulted before specifying.

Looking for specific information on the sustainability credentials of this product?