Mains Supply
230Vac +/- 10%; 50Hz
230Vac +/- 10%; 50Hz
Networking
LonWorks network TP/FT-10 (Capacitor decoupled)
DALI on output port pins 5 and 6 (COMPFYLCM)
LonWorks network TP/FT-10 (Capacitor decoupled)
DALI on output port pins 5 and 6 (COMPFYLCM)
Outputs
10 x independently addressable outputs
Emergergency light test instigation
Connections: Output female socket (Wieland GST18i6 male plug) *
Maximum total load: 16A total peak load (please refer to Whitecroft Lighting Technical Desk for load types)
Emergency maintained capacity: 1000VA total maximum
Digital dimming: 150mA maximum 15Vdc
Maximum 40 DALI addresses
10 x independently addressable outputs
Emergergency light test instigation
Connections: Output female socket (Wieland GST18i6 male plug) *
Maximum total load: 16A total peak load (please refer to Whitecroft Lighting Technical Desk for load types)
Emergency maintained capacity: 1000VA total maximum
Digital dimming: 150mA maximum 15Vdc
Maximum 40 DALI addresses
Inputs
4 dedicated switch inputs for retractive or latching Switches
4 DALI ports for COMPFRECPIR or COMPFSURPIR DALI sensors or COMPFSP DALI scene plates (max 10 x DALI sensors)
4 dedicated switch inputs for retractive or latching switches
4 DALI ports for COMPFRECPIR or COMPFSURPIR DALI sensors or COMPFSP DALI scene plates (max 10 x DALI sensors)
DALI Ports & Switch Inputs
Scene supply: 12Vdc +/- 5%, 30mA
Sensor isolation: 2kV
Scene supply: 12Vdc +/- 5%, 30mA
Sensor isolation: 2kV
Terminations
Mains input
LonWorks interface
DALI Bus connections
10 x outputs
Mains input
LonWorks interface
DALI Bus connections
10 x outputs
Conformity and Standards
Generic emission: EN 50081-1
Generic immunity: EN 50082-1
RFI: EN 55014
LonMark compliant
DALI compliant
Generic emission: EN 50081-1
Generic immunity: EN 50082-1
RFI: EN 55014
LonMark compliant
DALI compliant
Operating Temperature
0 C to +40 C
0 C to +40 C
Operating Humidity
10% to 90% non condensing
10% to 90% non condensing
Safety
EN 60950 Isolation: 4kV between mains and sensors/network/digital control
EN 60950 Isolation: 4kV between mains and sensors/network/digital control
Please note that these product properties are not a replacement for the manufacturer's literature and it is always recommended that Whitecroft Lighting is consulted before specifying.
|
|
||
| Temperature (?) | 0 °C | |
|
|
||
| Uniclass (?) | Pr_70_70_47 Lighting controls and lighting distribution products | |