Tested to the harmonised European Standard EN 1366-3:2009, Intumescent Pillows CE provide up to 2 hours fire stopping in rigid wall constructions.
CE marked to provide assurance where specified.
Firepro Intumescent Pillows CE are available in various sizes for packing into void spaces around services. Simple to install they are an ideal solution when installing additional services as they are easy to remove and reinstate.
Intumescent Pillows CE can be installed within rigid wall and rigid floor constructions. Intumescent Pillows CE are designed to create a temporary or permanent fire seal around all types of services to maintain continuity of fire performance of compartment walls and floors.
Under fire conditions, Intumescent Pillows CE expand several times their original volume to form an effective seal around service penetrations.
Please note that these product properties are not a replacement for the manufacturer's literature and it is always recommended that Rockwool Group is consulted before specifying.
|
|
||
| Application (?) | Cable trays/ladders , Metal pipework , Plastic conduits | |
| Product ID Number (?) | 301310 | |
| Quantity Per Pack (?) | 1 | |
|
|
||
| CE Marking (?) | ||
| Fire Rating (?) | 120 minutes | 100% |
|
|
||
| Location Suitability (?) | Internal | |
| Uniclass (?) | Pr_25_80_81_43 Intumescent pillows | |
|
|
||
| Airborne Sound Insulation (?) | 33 dB Rw + Ctr | |
| Features (?) | Dry system , Easy to install , High performance intumescent , Maintenance free , Suitable for rigid wall constructions , Up to EI120 fire resistance | |