ModuSat XR & XR-ECO Heat Interface Units

by Evinox

The complete solution for instantaneous hot water and indirect space heating in communal heating systems.

Heat interface units for indirect heating and instantaneous domestic hot water (DHW) with electronic PID control using Pressure Independent Control Valves (PICVs) with modulating actuators achieving a low primary return temperature as well as providing differential pressure control and flow rate regulation.

Heating

The heating circuit consists of a plate heat exchanger (PHE), PICV, safety relief valve, manometer, flow and return temperature sensors, Wilo PWM circulation pump and expansion vessel. The heating circuit flow temperature is controlled by the modulation of the primary flow rate with the integrated PICV actuator. Weather compensation is applied to the set heating temperature using SmartTalk 2-way communication. Suitable for radiators, Underfloor Heating or fan coil units.

Domestic Hot Water

Domestic hot water is heated via a separate plate heat exchanger and the temperature is regulated by the modulation of primary flow rate with the integrated PICV actuator. When fitted, the Lime scale reducer minimises lime scale formation.

ModuSat XR-ECO

Designed for modern low temperature heat networks, ModuSat XR-ECO units provide excellent heating and hot water performance at heat network primary flow temperatures as low as 60 C or even 55 C.

Features & Benefits

Independently Tested to the UK Standard for HIUs from BESA
Fast and Responsive DHW Performance
Designed for Modern Low Temperature Heat Networks
Low DHW Return Temperatures
Smart Connected Control
Integrated PaySmart technology ready for pre-payment billing upgrade
KIWA Approved Unit - Provides compliance with the UK Water Regulations
SmartTalk two-way communication for remote monitoring, control, alarms and diagnostics.
Mobile billing app available for use on smart phones and tablets.
Integrated heat meter MID approved and class 2 accuracy (BS EN 1434). Also capable of reading: Electrical Meter, Cold Water Meter & Chilled Water Meter
ViewSmart room controller with optional upgrade to provide ENE3 compliant smart metering
Option of top, bottom or combination connections
Various Metering & Billing Options Including remote monitoring, alarms and diagnostics
Optional casing and pipework insulation available
Integral hot water Mixing Valve for extra safety

Specification Details for ModuSat XR & XR-ECO Heat Interface Units (Heat Interface Units (HIU))

Please note that these product properties are not a replacement for the manufacturer's literature and it is always recommended that Evinox is consulted before specifying.

Looking for specific information on the sustainability credentials of this product?

File Downloads for ModuSat XR & XR-ECO Heat Interface Units

Clear selection

One-Click Quote